Volume 22, Number 10—October 2016
Dispatch
Reemergence of Mycobacterium chimaera in Heater–Cooler Units despite Intensified Cleaning and Disinfection Protocol
Table
Type of circuit | No. samples | Microbiology results, no. (%) samples |
||
---|---|---|---|---|
Any NTM growth | Mycobacterium chimaera | NTM other than M. chimaera | ||
Cardioplegia† | 48 | 14 (29.2) | 10 (20.8)‡ | 5 (10.4)‡ |
Patient† | 49 | 19 (38.8) | 12 (24.5)‡ | 8 (16.3)‡ |
Circuit not specified | 37§ | 5 (13.5) | 2 (5.4) | 3 (8.1) |
*NTM, nontuberculous mycobacteria.
†No statistically significant different results for water samples from cardioplegia and patient circuit (Fisher exact test, p = 0.554).
‡One culture had growth of both M. chimaera and M. gordonae.
§Six (16.2%) samples had bacterial overgrowth.
1Current affiliation: Unilabs, Dübendorf, Switzerland.
Page created: September 20, 2016
Page updated: September 20, 2016
Page reviewed: September 20, 2016
The conclusions, findings, and opinions expressed by authors contributing to this journal do not necessarily reflect the official position of the U.S. Department of Health and Human Services, the Public Health Service, the Centers for Disease Control and Prevention, or the authors' affiliated institutions. Use of trade names is for identification only and does not imply endorsement by any of the groups named above.