Legionella Infection Risk from Domestic Hot Water

Paola Borella*Comments to Author , M. Teresa Montagna†, Vincenzo Romano-Spica‡§, Serena Stampi¶, Giovanna Stancanelli#, Maria Triassi**, Rachele Neglia*, Isabella Marchesi*, Guglielmina Fantuzzi*, Daniela Tatò†, Christian Napoli†, Gianluigi Quaranta‡, Patrizia Laurenti‡, Erica Leoni¶, Giovanna De Luca§, Cristina Ossi#, Matteo Moro#, and Gabriella Ribera D’Alcalà**
Author affiliations: *University of Modena and Reggio E., Modena, Italy; †University of Bari, Bari, Italy; ‡Catholic University in Rome, Rome, Italy; §University Institute of Physics Sciences, Rome, Italy,; ¶University of Bologna, Bologna, Italy; #S. Raffaele Hospital, Milan, Italy; **University Federico II of Naples, Naples, Italy

Main Article

Table 6

Multiple logistic regression of system and water characteristics associated with Legionella contaminationa

Variable Legionella spp. yes/no

OR (95% CI)
Central heater
4.88 (1.61 to 14.76)b
Distribution site distance >10 m
4.55 (1.55 to 13.33)c
Zn <100 μg/L
0.22 (0.07 to 0.66)c
Heating system age >10 yr
3.68 (1.25 to 10.82)d
Cu >50 μg/L 0.08 (0.01 to 0.97)d

aOR, odds ratio; CI, confidence interval.
bp < 0.005.
cp < 0.01.
dp < 0.05.

Main Article

Page created: February 08, 2011
Page updated: February 08, 2011
Page reviewed: February 08, 2011
The conclusions, findings, and opinions expressed by authors contributing to this journal do not necessarily reflect the official position of the U.S. Department of Health and Human Services, the Public Health Service, the Centers for Disease Control and Prevention, or the authors' affiliated institutions. Use of trade names is for identification only and does not imply endorsement by any of the groups named above.