Environmental and Occupational Health Response to SARS, Taiwan, 2003
Table 4
Hospital | No. IR/no. PRc | Work shift | Shower outd | T&Be | % compliancef | No. SARS patients |
---|---|---|---|---|---|---|
DSH-1 |
102/un |
4 h |
Y |
Un |
100 |
45 |
DSH-2 | 92/210 | 8 h | Y | Un | 100 | 21 |
DSH-3 | 126/un | ND | Y | Un | 40 | 0 |
DSH-4 | 40/60 | 4 h | Y | Un | 100 | 0 |
DSH-5 | 42/80 | 3-2-3 h | Y | Y | 95 | 0 |
DSH-6 | 47/108 | 4 h | N | Un | 60 | 0 |
DSH-7 | 81/100 | 4 h | Y | Y | 95 | 0 |
DSH-8 | 72/un | 3 h | Y | Un | 70 | 0 |
DSH-9 | 78/un | 3 h | Y | Un | 90 | 0 |
DSH-10 | 28/49 | 3-2-3 h | Y | Un | 60 | 0 |
DSH-11 | 32/100 | 8 h | Y | Un | 100 | 0 |
aAll hospitals had a separate healthcare worker and patient path, single-pass air-handling units that provided 100% outside air with no recirculation, HEPA-filtered exhaust systems for the isolation rooms, UV light germicidal irradiation in the exhaust systems, and visible continuous negative pressure monitor with alarm that demonstrated the isolation room is operating under negative pressure.
bSARS, severe acute respiratory syndrome; DSH, dedicated SARS hospitals; un, unknown or unavailable at the time of the investigation; Y, yes; N, no; ND, not done.
cNumber of isolation rooms (IR) constructed and number of patient rooms (PR) previously at the hospital.
dPersonnel exiting the isolation ward are required to shower as part of the change-out protocol.
eFacility has completed a test and balance (T&B) (commissioning) of the ventilation system to verify proper function.
fPercentage of the construction completed.