Nosocomial Neonatal Legionellosis Associated with Water in Infant Formula, Taiwan
Table
Site of sampling | 1st Sampling,† strain (sequence type), concentration (CFU/L)‡ | 2nd Sampling,† strain (sequence type), concentration (CFU/L) | ||||
---|---|---|---|---|---|---|
Case 1 | ||||||
Tap water source 1 for bathing infants in nursery | L. pneumophila serogroup 4 (ST1712), 2.5x103 | L. pneumophila serogroup 4 (ST1712), TMTC | ||||
Tap water source 2 in nursery | L. pneumophila serogroup 4 (ST1712), 2x103 | L. pneumophila serogroup 4 (ST1712), TMTC | ||||
Drainage from air conditioner in nursery | ND | Negative | ||||
Tap water source in room adjacent to nursery | ND | L. pneumophila serogroup 4 (ST1764), TMTC | ||||
Cold water source of the hot/cold water dispenser§ | L. pneumophila serogroup 5 (ST1032)¶, 2.2x104 | ND | ||||
Tap water source in maternity ward |
ND |
Negative |
||||
Case 2 | ||||||
Tap water source for rinsing infants in nursery | Negative | Negative | ||||
Tap water source for reverse osmosis water in nursery | Negative | Negative | ||||
Cold water source of the hot/cold water dispenser§ | L. pneumophila serogroup 1 (ST1)¶, 2x102 | L. pneumophila serogroup 1 (ST1)¶, TMTC | ||||
Hot water source of the hot/cold water dispenser | ND | Negative | ||||
Tap water source 1 in maternity ward | Negative | Negative | ||||
Tap water source 2 in maternity ward | ND | Negative | ||||
Tap water source 3 in maternity ward | Negative | Negative | ||||
Tap water source 4 in maternity ward | ND | Negative | ||||
Tap water source for bathing in infant’s house | ND | Negative | ||||
Tap water source for drinking water in infant’s home | ND | Negative |
*Both case-patients were delivered by cesarean section and were not breast fed or placed in incubators. All potential infection sources were tested and listed. No humidifier was used in either nursery. ST, sequence type; TMTC, too many to count; ND, testing not done.
†The first samples from the environments of case-patients 1 and 2 were collected 33 d and 23 d after birth, respectively. The second samples were collected 34 d and 26 d after birth, respectively.
‡Concentration of Legionella spp. detected in water specimens, attributed to the presence of sampling swabs.
§Used in formula for neonates.
¶The pulsed-field gel electrophoresis profile of the strain was indistinguishable from that of the strain isolated from the patient’s sputum. The ST of the strain was the same as that of the strain isolated from the patient’s sputum.
1These authors contributed equally to this manuscript.